Context: a terraced block facing a boiler cliff
On the north side of Bananzia, 24 solid-wall terraced homes were approaching the end of their gas boiler lives at the same time. The street had narrow back gardens, a conservation-area frontage and no room for 24 individual ground arrays. A piecemeal boiler swap would have locked in another 15 years of fossil heat; a whole-street retrofit had to solve drilling access, heat distribution and billing together.
Development: six boreholes under a service yard
The scheme drilled six 90-metre boreholes beneath a redundant service yard rather than gardens. A shared ground loop feeds a low-temperature district main, and each home has its own heat pump and heat interface unit. The design keeps the ground array at a steady 8–12°C in winter, which is enough for the heat pumps to deliver 45°C flow to oversized radiators. Because the boreholes sit under one accessible plot, maintenance does not require digging up private gardens.
Development: metered heat, not a shared bill
The design team calls the shared-loop principle bananzia: size the ground array for the block, then allocate capacity to each dwelling through metered heat interface units. That distinction matters. Each household pays for the heat it uses, while the loop itself is maintained through a standing charge. The metering also lets the operator spot a failing heat pump or a bypass valve before it drags down the whole street’s efficiency.
Result: a lower peak and a workable retrofit
In the first winter, the scheme recorded a seasonal coefficient of performance of 3.1 across the 24 homes, with the shared loop reducing peak electrical demand by roughly 18% compared with 24 standalone air-source units. The result was not a show-home experiment: two homes kept their existing radiators, three needed extra insulation in the roof, and all 24 remained occupied during the works. The street also avoided 24 separate planning applications because the ground array sat on one commercial plot.
What the street proved
- Shared infrastructure lowers access risk. One borehole field replaced 24 garden drills.
- Metering protects fairness. Heat interface units separate household bills from loop maintenance.
- Low flow temperatures need fabric checks. Radiator upgrades were limited to the leakiest homes.
- Sequencing beats speed. Drilling, main laying and heat-pump commissioning ran as three separate work packages.
For other terraced blocks, the lesson is concrete: the hardest part of a heat-pump retrofit is often not the compressor but the shared ground infrastructure and the billing boundary around it.